Skip to main content

কীভাবে Wire Sizing গণনা করবেন

Wire Sizing কি?

Wire sizing selects conductor diameter to limit voltage drop and prevent overheating. Code requires ampacity matching and voltage drop limits.

সূত্র

Calculate voltage drop: VD = (2×K×I×L) / (1000×A) for DC or single-phase
VD
(2×K×I×L) / (1000×A) for DC or single-phase — (2×K×I×L) / (1000×A) for DC or single-phase
K
K value — Variable used in the calculation
I
I value — Variable used in the calculation
L
L value — Variable used in the calculation
A
A value — Variable used in the calculation
DC
DC value — Variable used in the calculation

ধাপে ধাপে নির্দেশিকা

  1. 1Look up ampacity from tables at operating temperature
  2. 2Calculate voltage drop: VD = (2×K×I×L) / (1000×A) for DC or single-phase
  3. 3Select wire where VD <3% feeder, <5% combined

সমাধান করা উদাহরণ

ইনপুট
I = 100 A, L = 50 m, copper wire, assume 60°C ampacity table
ফলাফল
AWG 6 (106 A) with ~3.1% drop, marginal
AWG 4 better choice

এড়ানোর সাধারণ ভুল

  • Using listed ampacity without derating for temperature or bundling
  • Neglecting voltage drop in long feeder runs

সচরাচর জিজ্ঞাসা

Why limit voltage drop?

Excessive drop reduces equipment performance, efficiency, and motor starting capability.

How does temperature affect wire sizing?

Higher temperature reduces ampacity; must derate if ambient >30°C.

গণনা করতে প্রস্তুত? বিনামূল্যে Wire Sizing ক্যালকুলেটর চেষ্টা করুন

নিজে চেষ্টা করে দেখুন →

সেটিংস