learn.howToCalculate
learn.whatIsHeading
Voltage Drop Calculator helps contractors and tradespeople accurately size, spec, and estimate materials and systems.
Fórmula
VD = (2 × K × I × L) / CM where K=12.9(Cu), I=amps, L=feet, CM=circular mils
Guía paso a paso
- 1Enter circuit amps, one-way distance, and wire gauge circular mils
- 2Apply the formula using your project measurements
- 3Add required safety factors or waste allowances per code
Ejemplos resueltos
Entrada
15A, 100 ft, 12 AWG (6530 CM)
Resultado
VD = (2×12.9×15×100)/6530 = 5.94V = 4.95% (max 3% recommended)
Errores comunes a evitar
- ✕Not applying code-required safety factors or derating
- ✕Forgetting to account for waste and cut losses in material estimates
learn.ctaText
Pruébalo tú mismo →