Cooling tower sizing removes waste heat to atmosphere. It's determined by cooling load and approach temperature to wet-bulb.

공식

Approach = outlet temp - wet-bulb temp (typically 2-4°C)
C
C value — Variable used in the calculation

단계별 가이드

  1. 1Calculate: Q = m×cp×ΔT where ΔT is cooling temperature drop
  2. 2Approach = outlet temp - wet-bulb temp (typically 2-4°C)
  3. 3Size tower for required cooling capacity

풀어진 예시

입력
Q = 500 kW, water flow 60 kg/s, approach 3°C, wet-bulb 25°C
결과
Tower outlet ≈ 28°C, inlet 36°C
6°C drop required

피해야 할 일반적인 실수

  • Confusing dry-bulb with wet-bulb temperature
  • Over-sizing tower (reduces efficiency)

자주 묻는 질문

How does wet-bulb affect cooling tower size?

Higher wet-bulb (humid climates) reduces cooling effectiveness; larger tower needed for same duty.

What's approach temperature?

Minimum difference between cooled water and wet-bulb; smaller approach requires larger (costlier) tower.