Heat exchanger effectiveness and sizing depend on flow rates, temperatures, and heat transfer area. Design ensures adequate thermal transfer.
공식
Calculate: Q = U×A×ΔT_lm (log mean temperature difference)
- Q
- U×A×ΔT_lm (log mean temperature difference) — U×A×ΔT_lm (log mean temperature difference)
- U
- U value — Variable used in the calculation
- A
- A value — Variable used in the calculation
단계별 가이드
- 1Calculate: Q = U×A×ΔT_lm (log mean temperature difference)
- 2Account for flow arrangement (counterflow, cross-flow, parallel)
- 3Size area for required heat transfer
풀어진 예시
입력
Q = 50 kW, U = 2000 W/m²·K, ΔT_lm = 10 K
결과
A ≈ 2.5 m² required
Determines exchanger size
피해야 할 일반적인 실수
- ✕Using arithmetic mean instead of log mean temperature difference
- ✕Neglecting fouling resistance
자주 묻는 질문
Why is counterflow more efficient?
Counterflow maximizes temperature driving force throughout; parallel-flow has smaller LMTD.
What determines overall U coefficient?
U depends on fouling, scale, fluid properties. Typical 500-5000 W/m²·K depending on fluids.