Wire sizing selects conductor diameter to limit voltage drop and prevent overheating. Code requires ampacity matching and voltage drop limits.
공식
Calculate voltage drop: VD = (2×K×I×L) / (1000×A) for DC or single-phase
- VD
- (2×K×I×L) / (1000×A) for DC or single-phase — (2×K×I×L) / (1000×A) for DC or single-phase
- K
- K value — Variable used in the calculation
- I
- I value — Variable used in the calculation
- L
- L value — Variable used in the calculation
- A
- A value — Variable used in the calculation
- DC
- DC value — Variable used in the calculation
단계별 가이드
- 1Look up ampacity from tables at operating temperature
- 2Calculate voltage drop: VD = (2×K×I×L) / (1000×A) for DC or single-phase
- 3Select wire where VD <3% feeder, <5% combined
풀어진 예시
입력
I = 100 A, L = 50 m, copper wire, assume 60°C ampacity table
결과
AWG 6 (106 A) with ~3.1% drop, marginal
AWG 4 better choice
피해야 할 일반적인 실수
- ✕Using listed ampacity without derating for temperature or bundling
- ✕Neglecting voltage drop in long feeder runs
자주 묻는 질문
Why limit voltage drop?
Excessive drop reduces equipment performance, efficiency, and motor starting capability.
How does temperature affect wire sizing?
Higher temperature reduces ampacity; must derate if ambient >30°C.
계산할 준비가 되셨나요? 무료 Wire Sizing 계산기를 사용해 보세요