Skip to main content

Wire Sizingని ఎలా లెక్కించాలి

Wire Sizing అంటే ఏమిటి?

Wire sizing selects conductor diameter to limit voltage drop and prevent overheating. Code requires ampacity matching and voltage drop limits.

సూత్రం

Calculate voltage drop: VD = (2×K×I×L) / (1000×A) for DC or single-phase
VD
(2×K×I×L) / (1000×A) for DC or single-phase — (2×K×I×L) / (1000×A) for DC or single-phase
K
K value — Variable used in the calculation
I
I value — Variable used in the calculation
L
L value — Variable used in the calculation
A
A value — Variable used in the calculation
DC
DC value — Variable used in the calculation

దశల వారీ గైడ్

  1. 1Look up ampacity from tables at operating temperature
  2. 2Calculate voltage drop: VD = (2×K×I×L) / (1000×A) for DC or single-phase
  3. 3Select wire where VD <3% feeder, <5% combined

పరిష్కరించిన ఉదాహరణలు

ఇన్పుట్
I = 100 A, L = 50 m, copper wire, assume 60°C ampacity table
ఫలితం
AWG 6 (106 A) with ~3.1% drop, marginal
AWG 4 better choice

నివారించాల్సిన సాధారణ తప్పులు

  • Using listed ampacity without derating for temperature or bundling
  • Neglecting voltage drop in long feeder runs

తరచుగా అడిగే ప్రశ్నలు

Why limit voltage drop?

Excessive drop reduces equipment performance, efficiency, and motor starting capability.

How does temperature affect wire sizing?

Higher temperature reduces ampacity; must derate if ambient >30°C.

లెక్కించడానికి సిద్ధంగా ఉన్నారా? ఉచిత Wire Sizing కాలిక్యులేటర్‌ని ప్రయత్నించండి

దీన్ని మీరే ప్రయత్నించండి →

సెట్టింగులు